Technical datasheet

Exostack EX-series modular exhaust stack

Aluminium exo-skeleton with replaceable coated-fabric duct. Reference configuration 7,000 mm installed height × 1,000 mm nominal internal diameter unless stated otherwise.

Rev 03 Sheet 1 / 1 Patent pending

1 — System description Architecture

A modular industrial exhaust stack in which structural duty and gas containment are carried by two independent elements. An external aluminium lattice exo-skeleton resists all mechanical load — self-weight, wind and guy pretension — and never contacts the flue gas. An internal coated-fabric duct contains the exhaust and carries no structural load. Radial stainless tensioning cables hold the duct in cylindrical form at every ring level while leaving it independently removable. Three guy wires transfer wind-induced overturning moment from the skeleton to distributed roof anchors, eliminating concentrated base moment and the roof reinforcement it would otherwise require.

Classification, Option BEN 1443 T260 N1 W
Structural designEN 1993-3-2 · ASCE 7
Product standardEN 13084-7
Operating pressureNegative (N1)
System mass, reference≈ 40 kg
Heaviest single module14 kg
Shipping2 Euro-pallets
Installation4–5 h, 2 persons

2 — Geometry and structure Envelope

Installed height range3,000 – 30,000 mm
Internal diameter range200 – 1,500 mm
Skeleton materialEN AW-6082 T651
Section jointsM12 stainless, flanged
Site weldingNone
Guy wires3 × 6 mm SS at 120°
Guy standardEN 12385, SF 3.0
Guy attachment2/3 height, integrated eyes
Base anchorsM16 stainless, 150 mm min
Skeleton design life30+ years

3 — Duct specifications Options A · B · C

ParameterOption AOption BOption C
Base fabricE-glass, 500 g/m²E-glass, 600 g/m²Para-aramid, 750 g/m²
Inner coatingSilicone, 200 g/m²PTFE, 400 g/m² minECTFE (Halar®)
Outer coatingUV siliconePVDF (Kynar®)PVDF (Kynar®)
Continuous temperature230 °C260 °C150 °C
Peak temperature250 °C300 °C170 °C
EN 1443 classT230 N1 WT260 N1 WT150 N1 W
Acid resistanceDilute onlyExcellentOutstanding
Abrasion resistanceModerateGoodExcellent
UV, xenon arc2,500 h3,000+ h3,000+ h
Fire performanceEN 13501-1 Cl. EEN 13501-1 Cl. EFM 4922
Duct service life8–12 years12–18 years15–20 years
Duct replacement cost€1,175–2,775€1,913–8,200€6,005–11,590
System mass, reference≈ 38 kg≈ 40 kg≈ 46 kg
Installed cost, reference≈ €9,000≈ €12,500≈ €17,500

4 — Installation Reference sequence

1 · Anchor base module60 min
2 · Bolt skeleton sections90 min
3 · Deploy and tension guys60 min
4 · Draw duct over skeleton60 min
5 · Test and record30 min
Total, one site visit4–5 hours
Crew2 engineers
Certification requiredWorking at height
Lifting plantNot required
Hot work permitNot required
Roof reinforcementNot required
Tools suppliedTensioning tool, gauge

5 — Inspection and service life Through life

Inspection intervalAnnual, ~30 min
Inspection scopeGuy tension, seams, base
Specialist visitNot required
Duct replacement time4 hours
Skeleton disturbedNo
Guy wire set life15–20 years

6 — Standards and approval status As published

European Union
EN 1993-3-2 structuralComplete
EN 1443 classificationComplete
IED dispersion methodComplete
DIBt approval (abZ)In progress
CE markingIn progress
EN 13501-1 fire testPlanned
United States
ASCE 7 wind designComplete
EPA stack methodComplete
OSHA manual handlingCompliant
NFPA 211 listingIn progress
UL 1777 listingIn progress
NRTL fire testingPlanned

7 — Application limits Do not specify outside these

Temperature — no option above 260 °C continuous; Option C limited to 150 °C. Pressure — negative pressure operation only, classification N1; sustained positive pressure is outside the design. Anchorage — three roof anchor points of adequate capacity and spread are required; without usable guy geometry the system cannot be installed. Abrasive and hot combined — abrasive particulate above 150 °C falls between the catalogue specifications and requires engineering review. Secondary loads — the skeleton is sized for the duct, wind and guy pretension only; cable trays, platforms, sampling equipment and antennas must not be attached.

8 — Scope of supply and documentation What ships

Skeleton modulesPer height
Base module and plate1 set
Coated fabric ductRolled, pre-formed
Guy assemblies3, swaged
Tensioning tool and gauge1 set
FixingsComplete
Declaration of PerformanceIncluded
Structural calculation reportProject specific
Vortex shedding assessmentEN 1991-1-4 Annex B
Dispersion calculationIED or 40 CFR 60
Installation manualIncluded
Commissioning recordIncluded

All figures are indicative and subject to project-specific engineering review. Prices are delivered and installed in Germany at 2025 rates and exclude VAT. Approval status is as published on this sheet and is updated as each workstream progresses — confirm current status before specifying. Teflon® is a registered trademark of The Chemours Company, Kevlar® of DuPont, Halar® of Solvay and Kynar® of Arkema.

Exostack · engineering@exostack.com · us@exostack.com · exostack.com · © 2026 · Patent pending

Next step

This sheet is generic. Your project is not.

Send us the stream, the geometry and the roof and we will return the same data calculated for your case — including the structural basis and a firm view on whether it fits.

Request a quote
ReplyWithin two working days, from an engineer rather than a mailbox
CostNothing, and no obligation